Motor protection lab
About this app
The tripping characteristic on a double-logarithmic scale, hands-on: setting and motor current via slider, overload in time-lapse up to thermal (bimetal) or magnetic tripping — with an animated functional model, a conveyor-belt practice exercise and a comparison of motor protection switch ↔ relay.
Two trip mechanisms
Motor protection combines two releases. A slow bimetal strip protects against overload: current heats it, it bends and after seconds to hours, depending on current, tips a trip lever. A magnetic release reacts to short circuits and trips in under 10 ms, typically from about 12 × Iₑ. The set current Iₑ is adjusted to the rated motor current Iₙ from the nameplate. The trip curve shows how long it takes to trip at each multiple of Iₑ, drawn as a band between cold and warm operating state.
What the app shows
The chart plots trip time against I/Iₑ on log-log axes, with thermal and magnetic regions. Sliders for set current Iₑ and motor current I, also draggable directly in the chart, move the operating point, and the app reads off the trip time. “Simulate overload” runs the clock, optionally in fast motion, until the device trips. A function model shows the bimetal, magnetic release and lever. A comparison panel explains the difference between a motor protection circuit breaker and an overload relay with contactor.
Conveyor belt exercise
The conveyor exercise sets Iₑ = 2.6 A. Find the motor current at which the device trips after about 10 s. Drag the current slider and watch the feedback: too little current, too much current, or already in the short-circuit range. The answer is around 13 A, about 5 × Iₑ, a genuine overload with thermal tripping. Note that up to about 1.05 × Iₑ continuous operation is allowed and the bimetal does not trip. The device type switch toggles between breaker and relay.
Frequently asked questions
- How do you read a motor protection trip curve?
- The horizontal axis shows current as a multiple of the set current, the vertical axis shows trip time, both on logarithmic scales. For a given current you read off how long the device takes to trip. The curve is a band because a cold motor trips later than one at operating temperature.
- What current should a motor overload protection be set to?
- The set current Iₑ is adjusted to the rated motor current Iₙ shown on the nameplate. The thermal release then trips on overload in line with the heating of the motor. Short-circuit protection is provided by the magnetic release or upstream fuses.
- What is the difference between a motor protection circuit breaker and an overload relay?
- A motor protection circuit breaker combines protection and switching and disconnects the main circuit itself on overload and short circuit. An overload relay is a thermal sensor mounted on a contactor: it opens its 95/96 contact in the control circuit, and the contactor disconnects the motor. Short-circuit protection then comes from fuses.
- What exercise does the motor protection lab include?
- The conveyor belt task: with Iₑ = 2.6 A you look for the motor current that trips the device after about 10 s. While you drag the slider, the app tells you whether the current is too low, too high or already in the short-circuit range.
Subject: Electrical & Control Engineering
More from Electrical & Control Engineering
- Three-phase asynchronous motor (3D)
- A week of power
- Power contactor (3D)
- Cable decoder
- Electric arc & arc-suppression elements
- Diagram-types explorer
- Circuit-symbol trainer
- Contactor circuit simulator
A VisuApp by heyprof: interactive, free in your browser, no sign-up. What is a VisuApp? · All apps