Star-delta starting

About this app

Motor with a heavy inertial flywheel (flying shear): direct start vs. Y start compared — I(t) and n(t) curves live, the winding schematic morphs between star (230 V, ⅓ current) and delta (400 V). Switch manually or via a timer relay; switching too early reveals the current surge.

Why star-delta starting?

A three-phase motor started direct-on-line draws a multiple of its rated current, up to 8 × Iₙ in the app. With a heavy flywheel the run-up takes a long time and loads the supply, fuses and cables. In star-delta starting the motor first runs in star connection: each winding sees 230 V instead of 400 V (factor 1/√3). Line current drops to ⅓ overall, so 8 × Iₙ becomes about 2.7 × Iₙ. Since torque scales with U², it also drops to ⅓, and the run-up takes longer.

What the app shows

A motor drives a heavy flywheel, as in a mechanical shear. You choose between direct-on-line, manual and automatic star-delta starting. The curves I(t) and n(t) are drawn live, with the direct start kept as a reference. The circuit panel shows the winding diagram switching between star (star point connected) and delta (windings in a ring), along with phase voltage, current ratio and torque. A status line describes the phases: star start, changeover gap (K3 opens, K2 closes) and delta operation.

Test the changeover moment

In manual mode you press Y→Δ yourself. Try switching early and late: if you change over while the motor is still slow, current jumps almost to the direct-start value, and the app reports the surge as a multiple of Iₙ. Close to rated speed only a small residual surge remains. In automatic mode a timer relay takes over, adjustable from 3 to 15 s. After switch-off the heavy flywheel coasts for a long time. Soft starters and variable frequency drives are modern alternatives.

Frequently asked questions

Why is the starting current in star connection one third?
In star, each winding sees 230 V instead of 400 V, so phase current drops by a factor of 1/√3. In delta, line current is also √3 times the phase current, while in star both are equal. Together this gives 1/√3 · 1/√3 = ⅓ of the line current of a direct start in delta.
What happens if a star-delta starter switches over too early?
If the motor has not yet reached high speed at changeover, it draws almost the full starting current in delta, as with a direct start. The benefit of the star start is lost. That is why changeover happens near rated speed, usually via a timer relay.
When is star-delta starting suitable?
It suits motors that run in delta at 400 V and start against a low load torque, because starting torque drops to ⅓. For starts under heavy load or with precise speed control, soft starters or variable frequency drives are often used today.
What can I adjust in the star-delta app?
You choose direct, manual or automatic starting and set the timer relay between 3 and 15 s. In manual mode you decide the changeover moment yourself and see the resulting current surge in the curves.