About this app

Reversal of direction by phase swap: a complete circuit diagram with K1/K2, latching and break-contact interlocking. Interlock can be disabled — anyone who then switches both directions provokes the phase short circuit with a flash and tripping fuses.

Reversing a motor

A three-phase motor reverses its direction when two line conductors are swapped. A forward-reverse starter uses two contactors for this: K1 connects L1, L2, L3 straight to the motor (forward), K2 feeds L1 and L3 crossed (reverse). Both contactors latch via auxiliary contact 13/14. If K1 and K2 pulled in at the same time, L1 and L3 would be connected directly through the main contacts: a phase-to-phase short circuit. The two contactors must therefore be interlocked.

Contactor and pushbutton interlock

With a contactor interlock, the coil circuit of each contactor contains a normally closed contact of the other, for example K1 21/22 in the K2 path. The rule is then: stop with S0 before reversing. A pushbutton interlock uses buttons with both a break and a make contact: the button for the other direction drops the running contactor and allows direct reversal. On its own it is not sufficient, because welded or bouncing contacts are only caught by the contactor interlock. Real reversing contactors are also mechanically interlocked.

Try it yourself

S1 starts forward, S2 starts reverse, S0 stops; the buttons can also be clicked directly in the diagram. The diagram shows the main and control circuits with highlighted current paths and marks the L1 ↔ L3 swap. The state panel shows K1, K2, motor speed and the active interlock. Switch the interlocks off one by one: without the contactor interlock you can engage both directions, the app shows the short circuit with a flash and fuses F1 blow. “Reset” fits new fuses.

Frequently asked questions

How do you reverse a three-phase motor?
You swap two of the three line conductors, for example L1 and L3. This reverses the rotating field in the stator and the rotor follows. In control engineering this is done with a forward-reverse circuit using two contactors.
Why does a reversing contactor circuit need an interlock?
Without an interlock both contactors could close at the same time. Since K2 connects two line conductors crossed, this would short two phases directly. The interlock prevents both contactors from being closed together.
What is the difference between a contactor interlock and a pushbutton interlock?
In a contactor interlock, a normally closed contact of one contactor blocks the coil circuit of the other. In a pushbutton interlock, the buttons block each other through their break contacts and allow direct reversal. Only the contactor interlock also protects against welded contacts, so both are combined.
Can I trigger the short circuit in the app?
Yes. If you disable the contactor interlock and start both directions at once, the app shows the L1–L3 phase short circuit with the fuses blowing. “Reset” makes the system ready again.

Subject: Electrical & Control Engineering